Specifications:
1) Rated voltage: 440V / three phase
2) Power range: 5.5 ~ 55kW
3) Output frequency: 0.1 ~ 400Hz
Features:
1) Automatic setting for acceleration / deceleration
2) 16-level preset table speed, switch of 4-level accelerating/decelerating time
3) RS-485 in-line interface build-in
4) Automatic control of motor parameters, precise location control
5) Automatic voltage regulation (AVR)
6) All-dimensional protection
7) Includes PID circuit control
8) Senseless vector control
9) Program and vector control of fan and water pump makes it more economical.
Input Voltage Level | 440V level |
ModelS3000-***/***43* | 055 | 075 | 110 | 150 | 185 | 220 | 300 | 370 | 450 | 550 | 750 |
Apply for rated power of | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | 75 |
3-f MOTOR(KW) |
Apply for rated power of | 7.5 | 10 | 15 | 20 | 25 | 30 | 40 | 50 | 60 | 75 | 100 |
3-f MOTOR(HP) |
Contant torque output | 13 | 18 | 24 | 32 | 38 | 45 | 60 | 73 | 91 | 110 | 150 |
current |
Variable torque output | 16 | 22 | 30 | 40 | 47 | 56 | 75 | 91 | 113 | 138 | 188 |
cureent |
Rated output capacity(kva) | 9.9 | 14 | 18 | 24 | 29 | 34 | 46 | 56 | 69 | 80 | 100 |
Maximum output voltage(v) | Three-phase power supply 380~440V corre |
sponding to input voltage |
Rated input voltage/frequency | 380/400/415/440Vcorrespongding to input |
voltage |
Operating voltage/frequency | 340~500VAC, 47~63Hz |
Control system | Selection of sine wave PWM |
vector control; torque control; V/F |
Activating torque | Activating toque is more than 150%in0.5HZ |
Control range of speed | 1: 100(can be up to 1: 1000 when have |
external PG) |
Control precision of speed | +-0.5%(can be up to +-0.02%) |
Speed reactivity | 5Hz(can be up to 30Hz under vector control) |
Maximum output frequency(HZ) | 0.00 to 400.00Hz |
Frequency output precision | Digit instruction +-0.005%, |
analog instruction +-0.5% |
Frequency setting resolution | Digit instruction 0.01Hz, analog instructio |
n: maximum output frequency is 1/1000(bit) |
Torque limit | Maximum 200% torque current |
Torque precision | +-5% |
Accelerating/deceleratingtime | 0.00~600.00 seconds/0.00~6000.00 seconds |
V/F curve | Randam V/F curve based on four points& |
quadratic curve |
Frequency setting signal | +10V, +-10V, 4~20mA, pulse wave input |
Dynamic brake | About 20% |
Motor protection | Electronic thermocouple protection |
` | Current restrain 170%, over-current protect |
ion 200% of rated current |
Ground protection for current | Current leakage protection; 50% peak value |
leakage | of rated current |
Overload capacity | Constant/variable torque 150% for |
60 seconds, 200% for 2 seconds |
Voltage protection | Over-voltage position: Vdc> 400/800v |
low-voltage position: Vdc< 200/400v |
Over-voltage protection for | Surge wave absorber(MOV) |
input power supply |
Over-heat protection | Built-in temperature sensor |
instantaneous power-off | Parameter setting can be up to 5 seconds |
compensation |
Protection level | NEMA 1/IP21 |
Operating temperature | -10 ~ 40 for UL & -10 ~50 for CE |
Storage temperature | -20 ~60 |
Humidity | Below 90%RH(non-condensing) |
Vibration | 1.0G below 20Hz, 0.6G at 20~60HZ |
Cooling system | Air-blasst cooling(RUN, STOP) |
Mounting height | Lower than 1000m |
Keep from corrosive gases, liquid and dust |