Customization: | Available |
---|---|
Application: | General Transducer |
Output Type: | Triple |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Items |
S900GS |
||
Power Supply |
Rated voltage, Frequency |
Single phase/Three phase 220V 50/60Hz |
|
Voltage Range |
220V:170V~240V 380V:330~440V |
||
Output |
Voltage Range |
220V:0~220V 380V:0~380V |
|
Frequency Range |
0.10~400.00Hz |
||
Control method |
V/F control, Space vector control. |
||
Indication |
Operating status/Alarm definition/interactive guidance: eg , frequency setting, the output frequency/current, DC bus voltage, the temperature and so on. |
||
Control Specifications |
Output Frequency Range |
0.10Hz~400.00Hz |
|
Frequency Setting Resolution |
Digital input:0.01Hz, analog input:0.1% of maximum output frequency |
||
Output Frequency Accuracy |
0.01Hz |
||
V/F Control |
Setting V/F curve to satisfy various load requirements |
||
Torque Control |
Auto increase: auto raise torque by loading condition; manual increase; enable to set0.0~20.0% of raising torque |
||
Multifunctional lnput Terminal |
Six multi-function input terminals, realizing functions including fifteen section speed control, program running, four-section acceleration/deceleration speed switch, UP/DOWN function and emergency stop and other functions |
||
Multifunctional Output Terminal |
2 multi-function output terminals for displaying of running, zero speed, counter, external abnormity, program operation and other information and warnings |
||
Acceleration/deceleration Time Setting |
0~-999.9s acceleration/deceleration time can be set individually |
||
PID Control |
Built-in PID control |
||
RS485 |
Standard RS485 communication function(MODBUS) |
||
Frequency Setting |
Analog input:0 to 10V,,0 to 20mA can be selected; Dig ital input: Input using the setting dial of the operation panel or RS485 or UP/DOWN |
||
Multi-speed |
Six multifunction input terminals, 15section speed can be set |
||
Automatic voltage regulation |
Automatic voltage regulation function can be selected |
||
Counter |
Built -in 2group of counters |
||
Protection/ Warning Function |
Overload |
150%,60 second(Constant torque) |
|
Over Voltage |
Over voltage protection can be set |
||
Under Voltage |
Under voltage protection can be set |
||
Other Protections |
Overheat, short circuit, over current, and parameter lock and so on |
||
Environment |
Ambient Temperature |
-10ºC to 40ºC(non-freezing) |
|
Ambient Humidity |
Max.95%(non-condensing) |
||
Altitude |
Lower than 1000m |
||
Vibration |
Max. 0.5G |
||
Structure |
Cooling Mode |
Forced air cooling |
|
Protective Structure |
IP20 |
||
Installation |
Mode |
Wall Mounted |